Electrical Machines 101 · Synchronous Machines

Synchronous generator under load: isolated island vs. infinite bus

Xs = 0.60 pu · Ra = 0 · linear OCC

Terminal voltage Vt 1.017 pu · +1.7% vs nominal
Machine state Within ±5% δ = 19.4° · stable
Load angle δ 19.4° Ea leads Vt
Real power P 0.733 pu · 74% of Pmax
Reactive power Q 0.354 pu · supplied
Voltage regulation 27.8% (Ea − Vt) / Vt

Load & excitation

0.80
0 (no load)1.50 pu
0.899 lag
← leadinglagging →
θ = +26° · inductive load
1.30
0.202.00 pu
|Ea| = 1.300 pu (Ea = K·If)

Phasor diagram — phase a

Power–angle characteristic

Operating point — numeric view

Every quantity in per unit unless marked. Phase angles are referred to Vt.

Quantity Symbol Magnitude Angle Note